S-K Systems Fuel Oil Pump and Heater Sets are designed to exceed minimum requirements of the burner with adequate safety factor to provide for eventual mechanical wear and future demand increases. Minimum reserve pump capacity considered, over peak burner demand is 40%.

Serviceability:
S-K Systems Pump and Heater Sets requiring maintenance, such as packing glands, bearing and oil points and regulator adjusting nuts are located for easy access. Gate valves in suction and discharge of duplex sets not only permit continuous operation during inspection or repairs, but also permit either pump to supply to either heater while the remaining pump or heater is serviced.

Installation:
Complete skid mounted assembly makes it possible to install our package in a minimum of time as connections need only by made to oil and steam supply, burner bypass and relief connections.

We Solicit All Special Requirements For Custom Packages

* Model Prefix
GPH Burning Rate
GPM Pumping Rate
Boiler HP
Lbs. Steam per hour
Inlet Size
Discharge Size
Recommended
Suction Line Size (150 ft. or under)
Recommended
Discharge Line Size (150 ft. or under)
Steam Supply Size Min. I.P.S.
Temperature
Regulator Size (100 PSI avg. Steam Press.)
1
60
1.4
200
7,200
1-1/2"
1"
1-1/2"
1
1/2"
1/2"
2
120
3.0
400
14,400
1-1/2"
1"
2"
1-1/4"
1/2"
1/2"
3
180
4.5
600
21,600
1-1/2"
1"
2"
1-1/4"
1/2"
1/2"
4
240
5.8
800
28,800
1-1/2"
1"
2-1/2"
1-1/2"
3/4"
1/2"
5
300
6.6
1000
36,000
2"
1-1/4"
2-1/2"
1-1/2"
3/4"
3/4"
6
360
9.0
1200
43,000
2"
1-1/4"
3"
2"
3/4"
3/4"
8
480
11.0
1600
57,600
2"
1-1/4"
3"
2"
3/4"
3/4"
10
600
13.0
2000
72,000
2-1/2"
1-1/2"
3"
2"
1"
3/4"
15
900
20.0
3000
108,000
2-1/2"
1-1/2"
3"
2"
1"
1"
20
1200
26.0
4000
144,000
3"
2"
4"
2-1/2"
1"
1"
30
1800
40.0
6000
216,000
4"
2-1/2"
4"
2-1/2"
1-1/4"
1"
40
2400
52.0
8000
288,000
4"
3"
5"
3"
1-1/2"
1-1/4"
50
3000
65.0
10000
360,000
5"
3"
5"
3"
2"
1-1/2"

* Model for Unit is designated by "EPH" followed by "S" or "D" for single or duplex, followed by Model prefix plus figure designating 1/10th pressure (i.e. 100 PSI oil discharge pressure would be "10", 250 PSI would be "25") followed by designation of type of each pump. (EE would be two electric, ES would be one steam one electric).

Click Here to Request a Heavy Fuel Oil Pump & Heater Set Quote
Click Here to Request More Information




Host of the Mid-Atlantic Pump and Process Equipment Symposium since 2000
©2007 Geiger Pump and Equipment Co., (410) 682-2660 | (610) 459-1212,

Legal Information